Loopcard
Overview
RE-LC Loop Card for AVANI, intelligent addressable fire alarm control panel. Up to 254 devices can be connected to a single loop card. These loop card can plugged in to slot provided in the motherboard of Main panel (Avani). RE-LC Loop Card is compatible with Addressable Detectors, Manual Call Points, Modules etc., The status of the loop shown by dual colour LED.
- Features
- Tech Specifications
- Downloads
- Certificates
- Tools
- Auto learning facility.
- Loop wise device test .
- Maximum 254 devices (any combination) per loop.
- Loop card can programmable as Class A, Style 5,6 or 7 and Class B Style 4 wiring.
Signaling Line Circuit
No of Devices per loop | : | 254 Devices. |
Loop resistance | : | 40 Ohms (Max.). |
Loop Capacitance | : | 0.6 micro farad (Max.). |
Loop current | : | 300 mA (Max.). |
Operating Voltage | : | 24 VDC |
Operating Temperature | : | 0-49 deg;C / 32-120 deg;F Ohms Max. |
Relative Humidity | : | 93 ± 2% RH (non-condensing) at 32 ±2° C/90 ±3° F. |
Compatible Panel
MODEL | DESCRIPTION |
---|---|
Avani | Analogue Addressable Fire Alarm Panel |
Ordering Information
MODEL | Description |
---|---|
RE-LC | Addressable Loopcard |
- CE Certificate
- MonitI Battery Calculator
- Configuration Tool