RE-2554
Overview
- The microprocessor based UL listed 4 Zone conventional fire alarm control panel, the system has 16 X 2 LCDcharacter,4 zones detection circuit,, 3 common potential free contacts &2 common NAC sounder output, inbuilt Rs-485 for repeater connectivity,wall/ceiling mounted, Switch mode power supply- SMPS & Battery polarity & Deep discharge protection.
- RE-2554 fire alarm control panel is designed with unique protocol to be used for small & medium establishments, Schools, hospitals, hotels, banks, commercial building, and small scale industries. The system is user friendly with includes all standard to ensure ease for use and high reliability.
- Special Features
- Tech Specifications
- Downloads
- Certificates
- Tools
- Switched Mode Power Supply.
- Modular Construction
- Auto Resettable Fuse
- Surge Protection for all Input and outputs.
- Programmable AC loss delay/Trouble Remainder/Alarm Verification
- Battery polarity reversible protection
- Surface Mount Technology
- Over All current consumption is low.
- Fully complies with UL -864 and NFPA-72.
- Rugged CRCA sheet with powder coated finish.
- Operates on 110 – 220v 50 /60 Hz, AC Mains power supply.
- 16×2 Dot Matrix LCD Display.
- 4/8 Class B Style ‘B ‘ or Style ’C’ initiating device circuit (IDC).
- All zones accept smoke detectors and any normally open contact device.
- Any Zone can be configured as Alarm or supervisory Zone.
- 2ClassBNotificationApplianceCircuits(NAC).
- NAC shall be programmed as silenceable or Non Silenceable.
- Supervisory Zone shall be Latching or Resettable.
- Standby (battery) backup 24v DC power supply with built in charger
- Error free Fire / Fault status in unambiguous colored LED indication.
- System ON indication.
- Main, Standby status audible and visual indication.
- Battery Low visual warning with audible tone.
- FormC relays for fire, fault and supervisory.
- Resettable / Steady 24V D.C. Output.
- RS 485 Communication facility (Optional).
- Lamp Test facility.
- All field wiring circuits are Power limited except 110 – 220v AC and Battery.
- All field wiring circuits are supervised.
- Walk Test facility.
- Zone Isolation facility with loop voltage cut off.
- Earth fault annunciation facility at 0 ohms.
- AC Low voltage cutoff.
- Programmable AC loss delay.
- Programmable Alarm verification.
- Programmable Trouble reminder.
Electrical Specification
Primary Power 120 – 220VAC ± 10%, 50 Hz, 2.5Amps.
Standby Power | Initiating Device Circuits All zones are Class B Style B/C operation (Programmable). Normal Operating Voltage: 14 – 21 VDC. Alarm Current: 15 – 30mA. Short Circuit Current: 45mA Maximum. Loop resistance: 100 ohms Maximum. End-Of-Line Resistor: 3K9, 1/2watt Standby Current: 7mA (2mA for Detectors) |
Operating Condition Operating Temperature 0 – 49° C/32-120° F. Relative Humidity 93 ± 2% RH (non- condensing) at 32 ±2° C/90 ±3° F. | |
Charging Circuit Charging Voltage 28.2V, ±0.5V Charging Current 800mA (Max.). | Notification Appliance Circuits Class B Style – Y wiring Operating Nominal Voltage: 24VDC Special Application Current for all NACs: 1.2Amps (0.6A per circuit) Line Drop: 1.8V End-Of-Line Resistor: 3K9, 1/2watt |
D.C. Output Supervised 24VDC regulated, 300mA Max. | |
Common Relays Type : Form C No of Relays : 3 Relay Contact Rating : 2Amps @ 30 VDC, 0.5Amps @ 125VAC. Power Factor : 1.0 |
Mechanical Specification
Dimensions | : | (440W X 340H X 120D) |
Color | : | Red / White |
Construction | : | 18 Gauge (1.22mm) CRCA sheet with powder-coated Finish |
IP Rating | : | IP50 |
Cable Entry | : | 11xø19mm Knockout in top of the cabinet 10xø22.25mm Knockout in top of the cabinet |
Ordering Information
Model | Description |
---|---|
RE- 2554-W | 4 Zones |
RE- 2554-R | 4 Zones |
Note:
W-White Color,
R- Red Color
Compatible Devices
Models | Description |
---|---|
RE-316S-2L | Photoelectric Smoke detector with base. |
RE-316H-2L | Heat detector with base. |
RE-316SH-2L | Photoelectric & Heat detector with base |
RE-314 | Common base for above |
RE-716MR | MCP Red |
RE-716MG | MCP Green |
RE-716MY | MCP Yellow |
RE-24CS | Mini Horn |
RE-24SS | Sounder cum Strobe |
RE-Monitor | 24VDC Output for Monitor Module |
RE-3K9 | End Of Line Resistor |
UL Certificate