RE-064 RP
Features
- 20 X 4 Dot Matrix LCD display.
- Alphanumeric keypads.
- RS-485 Communication for Network Repeater.
- System ON, AC ON, Battery ON, Charger ON indications.
- Drill test / Evacuate facility.
- Lamp test facility.
- Maximum 16 Mainpanels includes repeaters can be
- connected in a Single Network through RS-485.
- Special Features
- Tech Specifications
- Downloads
- Certificates
- Tools
- Ravel Indian Manufacturer, International standard.
- Operates on RS-485 communication.
- Repeats all the parameters of the main FACP.
Electrical Specification
AC Power :
120-220 VAC,60/ 50 Hz
Battery (Lead Acid only)
Charging Current : Constant Voltage – 27.6v @ 0.5A (Max.).
24V D.C (2 Nos of 12v, 7Ah (Max.) Sealed Lead acid battery)
System Quiescent Current : 70mA
Operating Condition
Operating Temperature : 0 – 49° C / 32-120° F.
Relative Humidity 93 ± 2% RH (non-condensing) at 32 ±2° C / 90 ± 3° F.
Notification Appliance Circuits (Sounder Circuit)
Operating Nominal Voltage : 24 VDC
Sounder (NAC) output : 0.5A
End-Of-Line Resistor : 4.7K, 1/4watt
Potential Free Relay Contact
Type : Form C
No of Relays : 1
Relay Contact Rating: 2 Amps @ 30 VDC,
0.5 Amps @ 125 VAC.
Mechanical Specification
Dimensions | : | (350W X 300H X 100D) |
Color | : | White |
Construction | : | 18 Gauge (1.22mm) CRCA sheet with powder-coated Finish |
IP Rating | : | IP50 |
Cable Entry | : | 11xø19mm Knockout in top of the cabinet |
Compatible Devices
Models | Description |
---|---|
RE-2554 / 58 | 4 / 8 Zone Fire Alarm Panel |
Ordering Information
Model | Description |
---|---|
RE- 008RP | Up to 8 Zones |
RE- 064RP | Up to 64 Zones |
RE-128RP | Up to 128 Zones |
CE Certificate
- Battery Calculator