RE-9128 – 128 Zones
Overview
The microprocessor based CE mark 96 Zone conventional fire alarm control panel, the system has 20 X 4 LCDcharacter with alpha numeric touch key pad, 96 zones detection circuit, 3 common programmable potential free contacts &4 common NAC sounder output, inbuilt Rs-485 for Networking – TCP/IP, peer to peer & repeater connectivity, central monitoring facility, inbuilt RTC with Event logs, wall/ceiling mounted, Switch mode power supply- SMPS & Battery polarity & Deep discharge protection.
RE-900 Series fire alarm control panel is designed with unique protocol to be used for small, medium & Large establishments, Schools, hospitals, hotels, banks, residential / commercial building, and small scale industries. The system is user friendly with includes all standard to ensure ease for use and high reliability.
- Special Features
- Tech Specifications
- Downloads
- Certificates
- Tools
- Complies with UL -864 and NFPA-72.
- 20 x 4 Dot Matrix LCD Display.
- Operates on 120 – 220v 60 /50 Hz, AC Mains power supply.
- Standby (battery) backup 24v DC power supply with builtin charger.
- Touch Keypad for user friendly operation.
- Epoxy powder coated finish.
- Class- B, Style B / C initiating device circuit (IDC).
- All zones accept smoke detectors and any normally open contact device.
- Class B Notification Appliance Circuits (NAC).
- NAC shall be programmed as auto silence / Silence Inhibit.
- Error free Fire / Fault status in unambiguous colored LED indication.
- 1000 Event storage with RTC.
- Main, Standby status with audible and visual indication.
- Two Form C relays for fire and fault.
- Resettable / Steady 24V D.C. Output.
- RS 485 Communication facility.
- TCP/IP facility (Optional)
- MODBUS for BMS integration (Optional).
- PC software (optional)
- External Zone Wise Sounder/Contact via RS 485 (Optional).
- All field wiring circuits are supervised.
- Zone Isolation facility with loop voltage cut off.
- Zones available : 12, 16, 20, 24, 32, 48, 64,96 and 128.
- Facility to connect Public Address System (PA) through RS-485 Communication.
- Peer to Peer network facility.
- Maximum 16 panels can be connect in a Single Network
Electrical Specification
Primary Power 120 – 220VAC ± 10%, 60 / 50 Hz. | Initiating Device CircuitsAll zones are Class B Style B/C operation (Programmable). Normal Operating Voltage: 14 – 21 VDC. Alarm Current: 15 – 30mA. Short Circuit Current: 45mA Maximum. Loop resistance: 100 ohms Maximum. End-Of-Line Resistor: 4K7, 1/2watt Standby Current: 7mA (2.5mA for Detectors) |
Standby Power 24V D.C Quiescent current : 120 mA | |
Operating Condition Operating Temperature 0 – 49° C/32-120° F. Relative Humidity 93 ± 2% RH (noncondensing) at 32 ±2° C/90 ±3° F. | |
Charging Circuit Charging Voltage 28.0V, ±0.5V Charging Current 1.2A(Max) | Notification Appliance Circuits Class B Style – Y wiring Operating Nominal Voltage: 24VDC Special Application Current from 12 Zone Upto 64Zone NACs : 2 Amps (1 A per circuit) Current above 64Zone NACs : 4 Amps (1 A per circuit) Line Drop: 1.8V End-Of-Line Resistor: 4K7, 1/2watt |
D.C. Output (Resettable / Steady) 24VDC Output ,1A Max.
Common Relays |
Dimensions
Zones | 425 | Height | Depth |
---|---|---|---|
12 Zone | 425 | 350 | 120 |
16 Zone | 500 | 350 | 120 |
20 Zone | 500 | 600 | 160 |
24 Zone | 500 | 600 | 160 |
32 Zone | 600 | 600 | 160 |
48 Zone | 600 | 700 | 160 |
64 Zone | 600 | 1000 | 160 |
96 Zone | 600 | 1400 | 160 |
128 Zone | 600 | 1400 | 160 |
All dimensions are in mm.
Ordering Information
Model | Description |
---|---|
RE-9012 | 12 Zone Fire Alarm Control Panel |
RE-9016 | 16 Zone Fire Alarm Control Panel |
RE-9020 | 20 Zone Fire Alarm Control Panel |
RE-9024 | 24 Zone Fire Alarm Control Panel |
RE-9032 | 32 Zone Fire Alarm Control Panel |
RE-9048 | 48 Zone Fire Alarm Control Panel |
RE-9064 | 64 Zone Fire Alarm Control Panel |
RE-9096 | 96 Zone Fire Alarm Control Panel |
RE-9128 | 128 Zone Fire Alarm Control Panel |
Compatible Devices
Models | Description |
---|---|
RE-900 Series | Fire Alarm Control Panel |
- CE Certificate
- IP Certificate
- Battery Calculator