Multi Sensor Detector

Overview

    UL Listed Analogue addressable Multi Sensor detectors with smoke detectors and the combination of heat detectors with the fixed temperature of 59 degrees Centigrade and Rate of raise facility of 11.1.Deg C /min with 8 digit dip switches for ( 1 to 254) address settings. Dual LED indication for 360-degree visibility, milky white in color, shall be polarity insensitive, easy to install, advanced detection and communication protocol with insect filter chamber.

 

  • UL Approved.
  • Dual LED’s for 360° visibility.
  • Advanced detection and communication protocol.
  • Polarity Insensitive.
  • Easy installation and maintenance.
  • Sleek low-profile housing design.
  • Regular 100mm base.
  • Max. 254 Address setting through 8 way DIP switch.

Electrical Specification

Operating Voltage:17 ~ 28V DC
Reset Voltage:less than 3V
Standby Current:500 µA
Alarm Current:7 mA.
Remote Output:2mA maximum open collector
Thermal Rating 59 °C (138 °F)
Rate of Raise of Temp:11.1°C / min (20°F/min)
Smoke Sensitivity:(2.12 ± 0.61) % / ft
High:1.1% ft
Middle:1.4% ft
Low:2.3% ft
Air Velocity:0 – 4000 fpm.
Operating Temperature:-10 °C to 50 °C
Humidity:0 – 95% RH, non-condensing

 

Mechanical Specification

Height:46 mm with base
Diameter:100 mm dia
Weight:150g with base
IP Rating:IP – 42

 

Compatible Devices

RE-314BNormal Base
RE-314BIIsolator Base

 

Ordering Information

MODELDESCRIPTION
RE317D-SHLAnalogue Addressable Photoelectric & Heat Detector

Wiring Diagram