RE-337 S
Features
- Complies with EN 54.
- Dual LED’s for 360° visibility.
- Advanced detection and communication protocol.
- Stable photoelectric smoke sensing chamber. No adjustment or replacement required
- Polarity insensitive.
- Easy installation and maintenance.
- Sleek low-profile housing design.
- Regular 100mm base.
- Simple Soft address programming for Easy installation.
- Tech Specifications
- Downloads
- Certificates
- Tools
Electrical Specification
Operating Voltage | : | 17 ~ 28V DC |
Reset Voltage | : | less than 5V |
Start-Up Current | : | 800 µA. |
Start-Up Time | : | less than 30s |
Alarm Current | : | 7 mA. |
Reset Time | : | less than 30s. |
Sampling Time | : | less than 1s. |
Remote Output | : | 2mA maximum open collector |
Operating Temperature | : | -10 °C to 50 °C |
Humidity | : | 0 – 95% RH, non-condensing |
Smoke Sensitivity | : | 0.09 dB/m ~ 0.14 dB/m. |
Mechanical Specification
Height | : | 46 mm with base |
Diameter | : | 100 mm dia |
Weight | : | 150g with base |
IP Rating | : | IP – 42 |
Mechanical Specification
Height | : | 46 mm with base |
Diameter | : | 100 mm dia |
Weight | : | 150g with base |
IP Rating | : | IP – 42 |
Compatible Device
RE-314B | : | Detector Normal Base |
RE-374BI | : | Detector Isolator Base |
MonitI | : | Addressable Single Loop FACP |
Ordering Information
MODEL | DESCRIPTION |
---|---|
RE-337S | Analogue Addressable Photo electric smoke detector |