Overview

    CE approved – Single Loop Analogue addressable fire alarm panel with 127 devices of any combination with 20 loop powered sounders in addition .supports single repeater panel,Touch key panel with USB inbuilt for Laptop connectivity. Front Panel programmable.

 

  • Switched mode power supply
  • Modular Construction, Serviceability
  • Surge Protection.
  • Battery polarity and deep discharge protection.
  • Unique protocol feature for fast alarm response.
  • Touch Keypad for user friendly operation.
  • Auto learning facility

Electrical Specification

Primary Power
120 / 220VAC + 10% -15%, 60 / 50 Hz
Standby Power
12V DC(1 No. of 12V,4.5Ah Sealed Lead acid battery)
Operating Condition
Operating Temperature : 0-49° C/32-120° F.
Relative Humidity : 93 ± 2% RH (non-condensing) at 32 ±2° C/ 90 ±3° F.
Signaling Line Circuits
Class A or Class B wiring.
No Devices : Max. 127 devices exclusive of loop sounder
Loop resistance : 40Ω (Max.).
Loop capacitance : 0.6 µf (Max.).
Loop Current : 300mA (Max.).
Notification Appliance Circuits
Class B, Style – Y wiring
Operating Nominal Voltage : 24 VDC
Current for NAC : 1.0A
Line Drop : 2.4V
End-Of-Line Resistor : 4K7, ½ watt
D.C. Output
24VDC regulated, 300mA Max.
Type : Form C
No of Relays : 1
Relay Contact Rating : 2A @ 30 VDC,0.5A @ 125VAC

 

Compatible Devices

MODELDESCRIPTION
RE-337-SHLPhotoelectric & Heat detector
RE-337-SLPhotoelectric smoke detector
RE-337-HLHeat detector
RE-737MCControl Module
RE-737MMMonitor Module
RE-737MRRelay Module
RE-737MZZoneModule
RE-737MXInput Output Module
RE-374BSSounder base
RE-374BIIsolator Base
RE-737MManual call point
RE-24ESLoop powered sounder

 