MonitI
Overview
- CE approved – Single Loop Analogue addressable fire alarm panel with 127 devices of any combination with 20 loop powered sounders in addition .supports single repeater panel,Touch key panel with USB inbuilt for Laptop connectivity. Front Panel programmable.
- Special Features
- Tech Specifications
- Downloads
- Certificates
- Tools
- Switched mode power supply
- Modular Construction, Serviceability
- Surge Protection.
- Battery polarity and deep discharge protection.
- Unique protocol feature for fast alarm response.
- Touch Keypad for user friendly operation.
- Auto learning facility
Electrical Specification
Primary Power 120 / 220VAC + 10% -15%, 60 / 50 Hz |
Standby Power 12V DC(1 No. of 12V,4.5Ah Sealed Lead acid battery) |
Operating Condition Operating Temperature : 0-49° C/32-120° F. Relative Humidity : 93 ± 2% RH (non-condensing) at 32 ±2° C/ 90 ±3° F. |
Signaling Line Circuits Class A or Class B wiring. No Devices : Max. 127 devices exclusive of loop sounder Loop resistance : 40Ω (Max.). Loop capacitance : 0.6 µf (Max.). Loop Current : 300mA (Max.). |
Notification Appliance Circuits Class B, Style – Y wiring Operating Nominal Voltage : 24 VDC Current for NAC : 1.0A Line Drop : 2.4V End-Of-Line Resistor : 4K7, ½ watt |
D.C. Output 24VDC regulated, 300mA Max. Type : Form C No of Relays : 1 Relay Contact Rating : 2A @ 30 VDC,0.5A @ 125VAC |
Compatible Devices
MODEL | DESCRIPTION |
---|---|
RE-337-SHL | Photoelectric & Heat detector |
RE-337-SL | Photoelectric smoke detector |
RE-337-HL | Heat detector |
RE-737MC | Control Module |
RE-737MM | Monitor Module |
RE-737MR | Relay Module |
RE-737MZ | ZoneModule |
RE-737MX | Input Output Module |
RE-374BS | Sounder base |
RE-374BI | Isolator Base |
RE-737M | Manual call point |
RE-24ES | Loop powered sounder |
Ordering Information
MODEL | Loop |
---|---|
MonitI | Single loop analogue addressable fire alarm panel |
- CE Certificate
- MonitI Battery Calculator
- Configuration Tool