Eazy beam DS
Product Overview
This device can be installed easily and quickly by a single person in single point of wiring & commissioning. It has special feature to compensate automatically for natural building movement to continuously maintaining alignment by building movement tracking technology.
Salient Features
- Auto alignment
- Easy Installation
- Standalone Detector
Salient Features
- Alignment mode switch, alignment directional buttons and configuration switches for alarm response threshold
- 2 Green LEDs and 1 Yellow LED for alignment status.
- System status : Green LED flashing every 10 sec in normal condition
Red LED flashing every 10 sec in alarm condition
Yellow LED flashing every 10 sec for obscuration or every 5 sec for contamination in Fault condition . - Flat front face with enclosed optics. Cleaning the optics does not affect alignment.
- UL Listed.
- Tech Specifications
- Downloads
- Certificates
- Tools
Specifications
Operating Voltage | : | 14 to 36 VDC |
Operating current | : | All operational modes – 5mA; Fast alignment mode – 33mA |
Operating temperature | : | -20 to +55°C |
Storage temperature | : | -40 to +85°C |
Relative humidity (non-condensing or icing) | : | 0 to 93% |
IP rating | : | Ip55 |
Housing flammability rating | : | UL94 V0 polycarbonate |
Optical Specifications
Fault level / Rapid obscuration (Δ ≤ 2 seconds) | : | ≥85% |
Maximum angular misalignment of Reflective Detector | : | ±0.5° |
Maximum angular misalignment of Reflector | : | ±5° |
Maximum angular alignment of Reflective Detector | : | ±4.5°(±70° with adjustment bracket accessory) |
Detection Performance
Detection range | : | 0 to 50m 0 to 120m with Reflective Long Range Kit |
Alignment method | : | Laser assisted, Auto-AlignmentTM. Manual alignment – optional setting |
Auto-AlignmentTM protocol | : | Background check, Box search, Adjust and Centre |
Building Movement TrackingTM | : | Compensates for natural shifts in alignment from building movement* |
Contamination Compensation | : | Compensates for gradual build-up of contamination on the optical surfaces |
Light Cancellation TechnologyTM | : | Compensates for high levels of sunlight and artificial lighting |
Optical wavelength – smoke detection | : | 850nm near infrared (invisible) |
Integrated laser – laser alignment | : | 650nm visible. Class IIIa <5mW |
Dynamic Beam Phasing | : | Allows beam detectors to be mounted facing each other with the reflectors in the middle. Eliminates false alarms caused by crosstalk between beams |
Signal output | : | Individual Alarm and Fault relays (VFCO) 2A @ 30 VDC |
Programmable User Settings
Alarm response threshold levels | : | 25% (1.25dB) – Fastest response to smoke 35% (1.87dB) – Default value 55% (3.46dB) – High immunity to false alarms, slow response to smoke 85% (8.23dB) – Highest immunity to false alarms, slowest response to smoke. Configured via the integrated user interface |
Delay to Alarm | : | 10 seconds, for momentary partial obstruction of the beam path |
Delay to Fault | : | 10 seconds, for momentary obstruction of the beam path |
Design Parameters
Separation distance between Detector and Reflector | : | 5 to 50m 50 to 120m with Reflective Long Range Kit |
Beam path clearance | : | 1m in diameter from centre line between Detector and Reflector |
Detector dimensions | : | 130W x 181H x 134D in mm (see diagram) |
Reflector dimensions | : | Up to 50m separation distance – Single reflector 100mm x 100mm x 9mm Up to 120m separation distance – Four reflectors arranged in a square patter 200mm x 200mm x9mm |
Product weight | : | Detector – 0.7kg; Reflector – 0.1kg |
Multi-detector arrangement | : | Dynamic Beam Phasing allows for Detectors to face each other with the reflectors in the middle |
Housing colour | : | White RAL9016, UV stable |
Field Wiring
Cable gauge and type | : | 2 core, dedicated, 0.5 to 1.6mm (24 to 14 AWG) System compatible with fireproof and non-fireproof cable meeting local installation standards |
Cable entry | : | 3 knock-out locations capable of accepting M20, 1⁄2″ or 3⁄4″ glands |
: | 4 drill-out locations capable of accepting glands up to 21mm diameter |
Test And Maintenance
Alarm test | : | Optical alarm test using Commissioning and Maintenance Kit accessory |
Ordering information
Model No | Part No | Description |
---|---|---|
EazyBeam | R60-024-1547 | Beam Detector – 50Mtrs |
EazyBeam | R60-024-1560 | Beam Detector – 120Mtrs |