RE-102R / 104 R

Overview

    The RE-102R & RE-104R is a 2 & 4 Zone Fire Alarm Control Panel, which uses conventional input devices. The Outputs include Notification Appliance Circuits (sounders), two programmable Form – C relays, RS-485 port to interface with annunciators and optional zone wise sounder & zone wise contact. The FACP is field programmable via the panel keypad. It also supervises all wiring, AC voltage and battery level. Optional ethernet, & GSM ports are user for transmission
    This Fire Alarm Control panel is designed to be used for small size commercial buildings and small-scale industries.

 

  • CE Approved.
  • 16 X 2 Dot Matrix LCD Display.
  • Standby battery backup with built in charging.
  • Switch Mode Power Supply.
  • Tactile Keypad for easy panel operation.
  • System ON indication.
  • Low Battery visual warning with audible tone.
  • Fire / Fault status in unambiguous colored LED indication.
  • 2 programmable relays for fire, supervisory and fault.
  • All zones accept smoke detectors and any normally open contact device.
  • Any Zone can be configured as alarm or supervisory.
  • Zone wise isolation and one man walk test facility.
  • Programmable Aux Outputs.
  • Lamp test & Drill test facility.
  • 100 All Events log with RTC.
  • Date / Time / Password configuration.
  • Programmable auto silence facility.
  • Zone wise sounder / contact (optional).
  • TCP-IP / GSM facility (optional).
  • All field wiring circuits are supervised.

Electrical Specification

Primary Power
120 / 230VAC + 10% -15%, 60 / 50 Hz, 50W
Standby Power
24VDC (2 Nos of 12V, 3.5Ah Sealed Lead acid battery)
Quiescent current   :   55mA
Operating Condition
Operating Temperature 0 – 49° C / 32 – 120° F.
Storage Temperature 0 – 60° C
Relative Humidity 93 ± 2% RH (non-condensing) at 32 ± 2° C / 90 ± 3° F
Quiescent Current
2 Zone
4 zone
40mA
50mA
Charging Circuit
Charging voltage
Charging current
28 V ± 5%
350mA (max)
24VDC
Quantity
Voltage
Current
1 No
24VDC continuous or resettable (Regulated)
100mA (max)
Notification Appliance Circuits
Wiring style
Quantity
Operating voltage
Current
EOL resistor
Class B
1 No
24VDC (Regulated)
350mA
4K7, 1/2 watt
Relays
Type
Quantity
Relay contact rating
Power factor
Form C
2 No’s (Programmable)
1A @ 30 VDC
1.0
Initiating Device Circuits
Wiring style
Quantity
Normal operating voltage
Alarm current
Short circuit current
Loop resistance
EOL Resistor
Standby Current
Class B
2 or 4 (102R- 104R)
14 – 21 VDC
15 – 35 mA
42 mA (max)
50 Ω (max)
4K7, ½ watt
6.8 mA (2.4 mA for detectors)
RS 485
Nodes
Wiring Style
Wire type
Circuit Length
Loop resistance
1
Class B
Twisted pair
1.2 Km (Max)
100 Ohms

 

Mechanical Specification

Dimensions:300L X 200W X 95D
Wire Size:1.5 Sq mm
IP rating:IP 60
Color:Black
Material:FRABS plastic
Cable Entry:11 x ø19mm Knockout on top of the cabinet

 

Ordering Information

ModelDescription
RE-102R2 Zone Fire Alarm Panel
RE-104R4 Zone Fire Alarm Panel

 

Compatible Devices

ModelDescription
RE-316S-2LPhotoelectric Smoke detector with base.
RE-316H-2LHeat detector with base.
RE-316SH-2LPhotoelectric & Heat detector with base
RE-716 MRConventional Manual Call Point.
RE-716P1TManual Pull station – Single action.
RE-716P1TLP (R)Manual Pull station – Dual action.
RE-25SSConventional Sounder cum Strobe
RE- 24 CSConventional Sounder.
RE-716SOConventional Sounder – UL Listed.
RE-716SOConventional Sounder cum Strobe – UL Listed.
RE-364BSConventional Sounder Base.

CE Certificate