RE-128 RP

Features

  • 20 X 4 Dot Matrix LCD display.
  • Alphanumeric keypads.
  • RS-485 Communication for Network Repeater.
  • System ON, AC ON, Battery ON, Charger ON indications.
  • Drill test / Evacuate facility.
  • Lamp test facility.
  • Maximum 16 Mainpanels includes repeaters can be
  • connected in a Single Network through RS-485.
  • Ravel Indian Manufacturer, International standard.
  • Operates on RS-485 communication.
  • Repeats all the parameters of the main FACP.

Electrical Specification

AC Power :
120-220 VAC,60/ 50 Hz

Battery (Lead Acid only)
Charging Current : Constant Voltage – 27.6v @ 0.5A (Max.).
24V D.C (2 Nos of 12v, 7Ah (Max.) Sealed Lead acid battery)
System Quiescent Current : 70mA

Operating Condition
Operating Temperature : 0 – 49° C / 32-120° F.
Relative Humidity 93 ± 2% RH (non-condensing) at 32 ±2° C / 90 ± 3° F.

Notification Appliance Circuits (Sounder Circuit)
Operating Nominal Voltage : 24 VDC
Sounder (NAC) output : 0.5A
End-Of-Line Resistor : 4.7K, 1/4watt

Potential Free Relay Contact
Type : Form C
No of Relays : 1
Relay Contact Rating: 2 Amps @ 30 VDC,
0.5 Amps @ 125 VAC.

 

Mechanical Specification

Dimensions:(350W X 300H X 100D)
Color:White
Construction:18 Gauge (1.22mm) CRCA sheet with powder-coated Finish
IP Rating:IP50
Cable Entry:11xø19mm Knockout in top of the cabinet

 

Compatible Devices

ModelsDescription
RE-2554 / 584 / 8 Zone Fire Alarm Panel

 

Ordering Information

ModelDescription
RE- 008RPUp to 8 Zones
RE- 064RPUp to 64 Zones
RE-128RPUp to 128 Zones

CE Certificate