RE-9128 – 128 Zones

Overview

The microprocessor based CE mark 96 Zone conventional fire alarm control panel, the system has 20 X 4 LCDcharacter with alpha numeric touch key pad, 96 zones detection circuit, 3 common programmable potential free contacts &4 common NAC sounder output, inbuilt Rs-485 for Networking – TCP/IP, peer to peer & repeater connectivity, central monitoring facility, inbuilt RTC with Event logs, wall/ceiling mounted, Switch mode power supply- SMPS & Battery polarity & Deep discharge protection.

RE-900 Series fire alarm control panel is designed with unique protocol to be used for small, medium & Large establishments, Schools, hospitals, hotels, banks, residential / commercial building, and small scale industries. The system is user friendly with includes all standard to ensure ease for use and high reliability.

  • Complies with UL -864 and NFPA-72.
  • 20 x 4 Dot Matrix LCD Display.
  • Operates on 120 – 220v 60 /50 Hz, AC Mains power supply.
  • Standby (battery) backup 24v DC power supply with builtin charger.
  • Touch Keypad for user friendly operation.
  • Epoxy powder coated finish.
  • Class- B, Style B / C initiating device circuit (IDC).
  • All zones accept smoke detectors and any normally open contact device.
  • Class B Notification Appliance Circuits (NAC).
  • NAC shall be programmed as auto silence / Silence Inhibit.
  • Error free Fire / Fault status in unambiguous colored LED indication.
  • 1000 Event storage with RTC.
  • Main, Standby status with audible and visual indication.
  • Two Form C relays for fire and fault.
  • Resettable / Steady 24V D.C. Output.
  • RS 485 Communication facility.
  • TCP/IP facility (Optional)
  • MODBUS for BMS integration (Optional).
  • PC software (optional)
  • External Zone Wise Sounder/Contact via RS 485 (Optional).
  • All field wiring circuits are supervised.
  • Zone Isolation facility with loop voltage cut off.
  • Zones available : 12, 16, 20, 24, 32, 48, 64,96 and 128.
  • Facility to connect Public Address System (PA) through RS-485 Communication.
  • Peer to Peer network facility.
  • Maximum 16 panels can be connect in a Single Network

Electrical Specification

Primary Power
120 – 220VAC ± 10%, 60 / 50 Hz.
Initiating Device CircuitsAll zones are
Class B Style B/C operation (Programmable).
Normal Operating Voltage: 14 – 21 VDC.
Alarm Current: 15 – 30mA.
Short Circuit Current: 45mA Maximum.
Loop resistance: 100 ohms Maximum.
End-Of-Line Resistor: 4K7, 1/2watt
Standby Current: 7mA (2.5mA for Detectors)
Standby Power
24V D.C
Quiescent current : 120 mA
 
Operating Condition
Operating Temperature 0 – 49° C/32-120° F.
Relative Humidity 93 ± 2% RH (noncondensing)
at 32 ±2° C/90 ±3° F.
 
Charging Circuit
Charging Voltage 28.0V, ±0.5V
Charging Current 1.2A(Max)
Notification Appliance Circuits
Class B Style – Y wiring
Operating Nominal Voltage: 24VDC
Special Application
Current from 12 Zone Upto 64Zone
NACs : 2 Amps (1 A per circuit)
Current above 64Zone
NACs : 4 Amps (1 A per circuit)
Line Drop: 1.8V
End-Of-Line Resistor: 4K7, 1/2watt
D.C. Output
(Resettable / Steady)
24VDC Output ,1A Max.

 

Common Relays
Type   :   Form C
No of Relays   :   2
Relay Contact Rating   :   2Amps @ 30 VDC,
0.5Amps @ 125VAC.
Power Factor   :   1.0

 

 

Dimensions

Zones425HeightDepth
12 Zone425350120
16 Zone500350120
20 Zone500600160
24 Zone500600160
32 Zone600600160
48 Zone600700160
64 Zone6001000160
96 Zone6001400160
128 Zone6001400160

All dimensions are in mm.

 

Ordering Information

ModelDescription
RE-901212 Zone Fire Alarm Control Panel
RE-901616 Zone Fire Alarm Control Panel
RE-902020 Zone Fire Alarm Control Panel
RE-902424 Zone Fire Alarm Control Panel
RE-903232 Zone Fire Alarm Control Panel
RE-904848 Zone Fire Alarm Control Panel
RE-906464 Zone Fire Alarm Control Panel
RE-909696 Zone Fire Alarm Control Panel
RE-9128128 Zone Fire Alarm Control Panel

 

Compatible Devices

ModelsDescription
RE-900 SeriesFire Alarm Control Panel
  • CE Certificate
  • IP Certificate
  • Battery Calculator