RE-127GR
Features
- 20 X 4 Dot Matrix LCD display.
- System ON, AC ON, Battery ON, Charger ON indications.
- Alphanumeric keypads.
- Drill test / Evacuate facility.
- Special Features
- Tech Specifications
- Downloads
- Certificates
- Tools
- Ravel Indian Manufacturer, International standard.
- Lamp test facility.
- Operates on RS-485 communication.
- Repeats all the parameters of the main FACP.
Electrical Specification
AC Power :
120-220 VAC,60/ 50 Hz
Battery (Lead Acid only)
Charging Current : Constant Voltage – 27.6v @ 0.5A (Max.).
24V D.C (2 Nos of 12v, 7Ah (Max.) Sealed Lead acid battery)
System Quiescent Current: 70mA
Operating Condition
Operating Temperature : 0 – 49° C / 32-120° F.
Relative Humidity : 93 ± 2% RH (non-condensing) at 32 ±2° C / 90 ± 3° F.
Notification Appliance Circuits (Sounder Circuit)
Operating Nominal Voltage : 24 VDC
Sounder (NAC) output : 0.5A
End-Of-Line Resistor : 4.7K, 1/4watt
Potential Free Relay Contact
1 No Fire Contact (2A@30VDC / 0.5A@125VAC)
Type : Form C
No of Relays : 1
Relay Contact Rating : 2 Amps @ 30 VDC, 0.5 Amps @ 125 VAC.
Mechanical Specification
Dimensions | : | (350W X 300H X 100D) |
Color | : | White |
Construction | : | 18 Gauge (1.22mm) CRCA sheet with powder-coated Finish |
IP Rating | : | IP50 |
Cable Entry | : | 11xø19mm Knockout in top of the cabinet |
Compatible Devices
Model | Description |
---|---|
RE-120GR | 2 Zone Gas Release Panel |
RE-25AR | 4 Zone Gas Release Panel |
Ordering Information
Model | Description |
---|---|
RE- 127GR | Gas Release Repeater Panel |
RE- 45AR | RS 485 Interface Module for RE-25AR |
Battery Calculator